Features
1. Automatic operating signals using power supply or dry contact
2. RPM, oil pressure gauge, oil temp gauge, water temp gauge , DC voltage, engine hour meter included
3. Relay capability included
4. Engine stops when engine pause button pressed, overspeed, oil pressure drop, high water temperature, over frequency, low frequency, voltage unbalance
5. Possible to stop engine when low voltage, over current, currentunbalance(according to setting)
6. If no MPU signal during the normal operation , engine stops
7. If no generating power during the normal operation, engine stops
8. Preheating function of engine preheating plug(automatic start)
9. Surge protection circuit
10. Anti humid and vibration by molding treatment
11. Mount on the front - easy to use
12. Engine operating signal and fault signal
Specifications
1. Power Input : 8~36Vdc
2. Commercial Power Detection : 500Vac, 3P4W or 1P
3. Overall(mm) : W240 * H170 * D62
4. Panel Cut-out(mm) : W211 * H158
5. Weight(kg) : 1
6. Operating Temp : -20~70℃
|